Send Message

Ningbo Suntech Power Machinery Tools Co., Ltd.

Professional Manufacturer and Exporter of Electric Power Field

Home ProductsHigh Voltage Cable Testing Equipment

900kV 4500kVA Series Resonance Test Set With Large Screen Display

900kV 4500kVA Series Resonance Test Set With Large Screen Display

  • 900kV 4500kVA Series Resonance Test Set With Large Screen Display
900kV 4500kVA Series Resonance Test Set With Large Screen Display
Product Details:
Place of Origin: Ningbo,China
Brand Name: Ningbo Suntech Power
Certification: ISO9001
Model Number: CHX(f)-400kW-4500kVA/300kV;900kV
Payment & Shipping Terms:
Minimum Order Quantity: 1set
Price: 142860USD-428570USD
Packaging Details: Wooden box
Delivery Time: 6-12 months
Payment Terms: T/T, Western Union, MoneyGram
Supply Ability: 1station months
Contact Now
Detailed Product Description
Name: Series Resonance Test System Specification: 400kW-4500kVA/300kV;900kV
Max.capacity: 4500KVA Test Frequency: 20Hz~400Hz
Rated Output Voltage: 900kV Rated Output Power Of Variable Frequency Power Supply: 400kW
Operation Hours: 60min Output Frequency Resolution: 0.01Hz
Variable Frequency Power Supply Capacity: 400kW (Push-pull Linear Amplification Type) Certificate: ISO9001
High Light:

4500kVA Resonance Test Set

,

AC High Voltage Resonant Test Set

Series resonance test system
 
1. The equipment meets the test requirements

Capable of AC withstand voltage test for primary equipment with voltage level of 500kV and below, test voltage 900kV, current 5A, test frequency 30~300Hz, withstand voltage test 60min
Variable-frequency power supply with ≥400kW without partial discharge variable-frequency power supply, frequency test frequency 30~300Hz
The excitation transformer is equipped with 400kVA without partial discharge excitation transformer,
Compatible with 110kV/630mm2 cross-section cable 2km, capacitance 0.188μF/km, capacitance not exceeding 0.376μF, test voltage 128kV, withstand voltage time 60min/phase;
Compatible with 220kV/630mm2 cross-section cable 2km, capacitance 0.138μF/km, capacitance not exceeding 0.276μF, test voltage 216kV, withstand voltage time 60min/phase;
Compatible with 110kV main transformer neutral point withstand voltage test, the maximum capacitance does not exceed 0.025μF, test voltage ≤140kV, withstand voltage time 1~15min; test frequency 45~300Hz
Compatible with 220kV main transformer neutral point withstand voltage test, the maximum capacitance does not exceed 0.025μF, test voltage ≤160kV, withstand voltage time 1~15min; test frequency 45~300Hz
Compatible with 110kV substation equipment: CT, GIS, switches, circuit breakers, bushings, etc., the maximum capacitance does not exceed 0.03μF, the test voltage is ≤270kV, and the withstand voltage time is 1-15min;
Compatible with 220kV substation equipment: CT, GIS, switches, circuit breakers, bushings, etc., the maximum capacitance does not exceed 0.03μF, the test voltage is ≤495kV, and the withstand voltage time is 1~15min;

 

Equipment use relation table during test

 

Equipment combination test object
1500kVA/300kV/5A/200H
Reactor three sections
Excitation transformer output selection
AC withstand voltage test of 500kV and below substation equipment, etc., the test voltage is 900kV
The capacitance does not exceed 0.03μF
Use three reactors in series
35kV
110kV/630mm² cable 2km, test voltage 128kV
0.376μF
Use three reactors in parallel
5kV
220kV/630mm² cable 2km, test voltage 216kV
0.276μF
Use three reactors in parallel
10kV
Compatible with 110kV main transformer neutral point AC withstand voltage test, test voltage 140kV
0.025μF
Single section using reactor
5kV或10kV
Compatible with 220kV main transformer neutral point AC withstand voltage test, test voltage 160kV
0.025μF
Single section using reactor
5kV或10kV
Compatible with 110kV voltage level GIS withstand voltage test, test voltage 270kV
0.03μF
Single section using reactor
10kV
Compatible with 220kV voltage level GIS withstand voltage test, test voltage 495kV
0.03μF
Use two strings of reactors
20kV

 

2,Main technical parameters of equipment
System technical indicators
Rated working input power: 380V±10% (three-phase); 50Hz
Rated output power of variable frequency power supply: 400kW
Rated output capacity: 4500kVA
Rated output voltage: 900kV
Output phase number: single phase
Frequency adjustable range: 20Hz~400Hz, when the frequency is adjusted within the set range, the voltage is constant output
Output frequency resolution: 0.01Hz
Output frequency instability: ≤0.05%
The output voltage waveform is a sine wave: waveform distortion rate ≤1.0%
Running time: 60min continuous running under rated capacity
Insulation level: withstand voltage for 1 min under 1.1 times the rated voltage
Quality factor: Q>60 (f=30Hz)
Variable frequency power supply capacity: 400kW (push-pull linear amplifier)

 

3,Main functions of the system:
1) The variable frequency power supply adopts a linear power amplifier circuit, which has a perfect sine wave output and low waveform distortion
2) With automatic voltage stabilization adjustment function
3) Safe and reliable. A variety of protections are integrated in this device, including: discharge breakdown protection, over-voltage, over-current setting protection, output short-circuit protection, boot zero protection, bridge arm amplifier circuit protection, power curve protection, etc. When any kind of protection appears, the device immediately blocks the test voltage output and cuts off the main circuit power supply to ensure the safety of the test personnel, the tested product and the test system
4) The high-voltage measurement signal is transmitted by optical fiber to completely isolate the high-voltage and low-voltage circuits
5) Two control modes: automatic/manual
6) 320*240 dot liquid crystal display and multiple rotating mice provide a friendly man-machine interface, easy and quick operation and wiring, and truly "just look at it"
7) Synchronous voltage, current and frequency display
8) The output frequency is continuously adjustable within the range of 20-300Hz
9) The output voltage is continuously adjustable within the range of 0~350V
10) With resonance withstand voltage test function
11) With automatic resonant frequency search function, multiple automatic frequency sweeping frequency bands can be set

 

4,System display function:
1) With a large screen display, it can indicate: output voltage, output current, frequency, ambient temperature, outlet air temperature, variable frequency power supply output voltage waveform, date and time, countdown time, fault information, etc.;
2) It has the function of setting test parameters such as test voltage and time;

 

5,Other features of the product:
1) The oil-filled equipment in the device does not leak oil.
2) All metal shells in the device are rust-proof and anti-corrosion treatment, and the coating is uniform and beautiful. The main components have stainless steel nameplates and terminal signs.
3) The device can be stored, assembled and disassembled indoors and outdoors; the protection function is complete. The manufacturer guarantees that the control equipment, transformers, reactors, etc. of the device are at 1.1 times the rated voltage, and if the high-voltage side sample flashovers to the ground during the test, it will not cause personal injury and the test equipment will not cause harmful mechanical and thermal stress. Electrical performance is damaged or damaged.
4) Each part of the equipment has a nameplate that conforms to the national standard, the words and symbols are clear and durable, and the nameplate is clearly visible when the equipment is in normal operation.

Contact Details
Ningbo Suntech Power Machinery Tools Co.,Ltd.

Contact Person: Peter

Tel: 86-13958364836

Send your inquiry directly to us
Other Products