Send Message

Ningbo Suntech Power Machinery Tools Co., Ltd.

Professional Manufacturer and Exporter of Electric Power Field

Home ProductsHigh Voltage Cable Testing Equipment

132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight

132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight

  • 132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight
132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight
Product Details:
Place of Origin: Ningbo,China
Brand Name: Ningbo Suntech Power
Certification: ISO9001
Model Number: CHX-275KVA/275KV
Payment & Shipping Terms:
Minimum Order Quantity: One Unit
Price: Negotiable
Packaging Details: Export Standard Wooden Case With Fumigation Free
Delivery Time: 25~45 work days
Payment Terms: T/T
Supply Ability: 10units/2months
Contact Now
Detailed Product Description
Test Principle: Variable Frequency Resonant Circuit Usage: AC Withstand Voltage Test Under 275KV
Max.capacity: 275KVA Max. Voltage: 275KV
Design Feature: Portable Type , Lighter Single Piece Weight, Special For On-site Installation And Test Component: V/F Power Source, Excitation Transformer,lighter Modular Test Reactor, And Voltage Divider
Test Frequency: 30-300Hz Duty Cycle: 60 Mints
Test Accuracy: No Less Than 1.5% Output Waveform: Good Sine Wave
Special For: On-site Test For 132 KV GIS And Medium Voltage Cable Reactor Using Way: In Series Or In Parallel Connection
Test Standard: IEC 60060-1:2010;IEC 62271-203:2011 For GIS, IEC 60840:2011 For XLPE Cable;
High Light:

GIS AC Resonant Test System

,

132KV AC Resonant Test System

,

AC Resonant Test Set

Portable Variable Frequency Resonant Withstand Voltage Test Set , For 132KV GIS Test

 

I. Application :


This test set model CHX-275KVA/275KV is designed for 132KV and below class GIS on-site AC withstand voltage test with variable frequency resonant circuit technology; the highest test voltage is no more than 275KV; test frequency: 30-300Hz; the duty cycle is no more than 60mints.

 

Through modular test reactor is used in parallel , the test set model CHX-275KVA/275KV also can be performed the following AC hipot test:

1. No more than 55KV and 5A for medium voltage XLPE cable , scuh as 45KV and below class.

2. No more than 110KV and 2A for medium voltage XLPE cable , scuh as 66KV and below class.

3. No more than 275KV and 1A for medium voltage GIS , scuh as 132KV~170KV and below class.

4. No more than 55KV and 5A for power motor or generator within 45~55Hz

5. Medium voltage switchgear and power transformer ,scuh as 132KV and below class.

 

Until now , these portable designed test set can form many different serialized model according to different medium votage withstand test applications through test reactors in series or in parallel connection and number of configurations in each set, The alike model can see other typical model at the following clause.


2. Main Components:

 

SN Name of Components Type and specification Qty. Each weight Each Dimension
1 Variable frequency power FKVF-20kW/380V 1piece 20kgs 440*360*360mm
2 Excitation transformer CQSB(J)-15kVA/15KV,3KV 1piece 50kgs 520*350*550mm
3 HV resonant test reactor CHX(kf)-55kVA/55kV 5pieces 60kgs D480*H520mm
4 Capacitive divider TRF-300kV/1000pF 1set 35kgs D170*H1850mm
5 Special test accessories   1set    

Note:1.Load capacitantor can be optional when testing power motor ,generator and power transformer under 45~65Hz.

2.Test reactor can be produced to be 18KV,20KV,22KV,40KV,44KV, 50KV, 54KV,55KV for each piece according to different tested object scope or customer requried.

 

III. Test priciple :
132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight 0

VF: Variable Frequency Power Source T : Excitation Transformer
L : Test Reactor Cx: Tested Equipment MOA1: Lightning Arrestor
C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm )


V.Test Wiring Schematic Diagram(for example) :
132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight 1

V. General Technical data:

  1. Mode of system test: Series resonant with variable frequency
  2. System model : FKTF-275KVA/275KV
  3. Input power supply : 380±10%(three-phase),50Hz/60Hz
  4. Rated inductance parameter: 55KVA/55KV/1A/200H/each
  5. Number of HV test reactor: 5pieces
  6. Rated output capacity: 275kVA
  7. Rated output Voltage: 275KV
  8. Max Test voltage : no more than 275KV
  9. Rated output current: 1A /single piece or in series;5A in parallal
  10. Reg. Freq range : 30Hz-300Hz
  11. Output Resonance voltage waveform: sine wave
  12. THD of output waveform: ≤1%
  13. Insulation level: Under 1.1 times and keeping 1min, normal
  14. Duty cycle : 60mins on under rated current working condition ;
  15. Quality factor of test set itself: Q≥30(at F=30HZ) ;
  16. Temperature rise: Less than 65K under rated current working 60mints;
  17. Noise level: No more than 70B
  18. Reactor Structure: dry type, epoxy tube cylinder type;


VI. Main Measuring and control software panel:
132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight 2
Note: This is the software panel before start test for parameter setting

VII .Delivery wooden case packing list

 

Case No. Packed goods name Model&spec. Goods qty.in the wooden case Wooden case dimension (cm) Case gross weight Case number Remark
6-1 VF power source FKVF-20kW 1piece 55*47*60 45kgs 1  
6-2 Excitation transformer CQSB(J)-15kVA 1piece 67*51*87 110kgs 1  
6-3 HV reactors CHX(kf)-55kVA/55kV 5pieces 141*98*82 619kgs 1 One case packing
Accessories box Including test cables and manual 1set
6-4 Voltage divider TRF-300kV-1000pF 1piece 178*57*51 80kgs 1  
6-5 Corona ring for divider ,reactor   1set 90*90*94 56kgs 1 One case packing
Supporting base for divider   1piece
6-6 Insulation supporting bases for reactor 28KV,165KV each one 2pieces 63*63*123 52kgs 1  
        Total 962kgs 6 wooden case  



VIII.Accessories

  • Accessory box for storage accessoires
  • Input cables of power source
  • Output cables of power source
  • Output cables of exciting transformer
  • System grounding cables
  • Parallel cables of the reactor
  • HV measuring cables ( the signal output cables of voltage divider )
  • HV output cables(reactor to divide,divider to test object)
  • Insulation supporting base
  • corona ring for 275KV test
  • A final test report, a quality Certificate ,a user manual and a packing list are offered .


IX. Other Optional Model

 

1. For GIS on-site test

Model Rated voltage Rated output current Rated output capacity

Application

(From 45Hz starting)

CHX-135KVA/135KV 27KV*5 1A 135KVA For 72.5KV and below GIS
CHX-270KVA/135KV 27KV*5 1A 135KVA For 72.5KV and below GIS
CHX-216KVA/216KV 27KV*8 1A 216KVA For 123KV and below GIS
CHX-270KVA/270KV 27KV*10 1A 270KVA For 145KV and below GIS
CHX-275KVA/275KV 275KV 2A 275KVA For 170KV and below GIS
Special requirement can be made by order

 

 

2. For 45KV XLPE cable on-site test

Model Rated voltage Rated output current Rated output capacity Max Application
CHX-108/54 54KV 2A 108KVA 45kV cable≤1km
CHX-216/54 54KV 4A 216KVA 45kV cable≤2km
CHX-324/54 54KV 6A 324KVA 45kV cable≤3km
CHX-432/54 54KV 8A 432KVA 45kV cable≤4km
CHX-540/54 54KV 10A 540KVA 45kV cable≤5km
CHX-1080/54 54KV 20A 1080KVA 45kV cable≤10km
Special requirement can be made by order

 

3. For 66KV XLPE cable on-site test

Model Rated voltage Rated output current Rated output capacity Max Application
CHX-160/80 80KV 2A 160KVA 66kV cable≤0.5km
CHX-320/80 80KV 4A 320KVA 66kV cable≤1km
CHX-640/80 80KV 8A 640KVA 66kV cable≤2km
CHX-960/80 80KV 12A 960KVA 66kV cable≤3km
CHX-1280/80 80KV 16A 1280KVA 66kV cable≤4km
CHX-1600/80 80KV 20A 1600KVA 66kV cable≤5km
CHX-3200/80 80KV 40A 3200KVA 66kV cable≤10km
CHX-9600/80 80KV 120A 9600KVA 66kV cable≤20km
Special requirement can be made by order

 

 

X. On-site insulation test standard table from IEC62271-203:2011 for GIS

132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight 3

 

XI. On-site insulation test standard table from IEC 60840:2011 for XLPE cable

132KV GIS Testing AC Resonant Test System Lighter Single Piece Weight 4

Contact Details
Ningbo Suntech Power Machinery Tools Co.,Ltd.

Contact Person: Peter

Tel: 86-13958364836

Send your inquiry directly to us